Clean Room

RapidRoll Clean.

 

Production in a controlled environment, such as a cleanroom, is common practice in many industries. Some examples are medical applications, research, electronics, pharmaceutical, semiconductor production and space flight. All components used in cleanrooms are subject to stringent requirements. Particularly in these areas, it is important to keep the production stations clean. In this connection, doors as components of cleanroom areas must prevent undesired air exchange and the uncontrolled entry of airborne particles. For this area, Albany has now expanded its product range with a new cleanroom door: RapidRoll® Clean. This is the first door that has been tested by the Fraunhofer Institute for cleanroom suitability.

 

  • Well suited to cleanroom isolation in accordance with DIN EN ISO 14644-1 Class 5.
  • Provides high air-tightness and keeps the pressure drop through the closed door at a minimum.
  • Fast opening and closing ensures very low air loss and minimize air exchange, which results in a low filter burden and increased cleanroom cost-effectiveness.
  • Smooth surface allows easy cleaning.
  • Design in accordance with GMP Class C.
  • Integrated cable guide for a smooth overall surface
  • Contactless actuator (optional) enables fast, hygienic opening with a simple hand motion.
  • Integrated traffic light (optional).
Technical Data
Options

Place of installation

 

Suitable for cleanrooms with pressure differences up to 50 Pa

 

Cleanroom class

 

ISO Class 5 – EN 14644-1

GMP  Class C

 

Leckage (door size1500 x 2000 mm)

 

20 m3/h at a pressure difference of  25 Pa

 

Door dimensions

 

Max HxW – 3500 mm x 3500 mm

 

Open / close up to max

 

2.0 / 1.0 m/s

 

 

Control systems / Drive unit

 

MCCVector Control with UPS,

Additional opening heights,

potential-free contacts  max. 250 V

 

Safety

 

Pre-running safety  photocell,

Automatic egress

 

Access system

 

no-touch Magic Switch